dc.description.abstractAxial shaft voltages have been investigated as a condition monitoring tool for turbo- generators. It was found that static air-gap eccentricity in a 20 kW, 2 pole syn- chronous generator, which was designed and built to mimic a larger 660 MW set, can be diagnosed using the shaft voltage. The shaft voltage in this experimental alternator has been simulated using 2D finite elements method (FEM) software. This software has been used to explain some of the causes of the shaft voltage in this generator. It was confirmed that shaft signals are primarily caused by construc- tional asymmetries. The FEM software has also been used to study the effects of various faults on the shaft voltage in a time efficient manner. These faults should be investigated experimentally in future work.en_ZA
dc.identifier.urihttp://hdl.handle.net/10539/11703
dc.language.isoenen_ZA
dc.titleThe analysis of shaft voltages in a synchronous generator with various induced faultsen_ZA
dc.typeThesisen_ZA
Files
Original bundle
Now showing 1 - 2 of 2
No Thumbnail Available
Name:
DdeCanha0204943W - MSc Abstract.pdf
Size:
12.96 KB
Format:
Adobe Portable Document Format
No Thumbnail Available
Name:
DdeCanha0204943W_MSc_Diss_signed.pdf
Size:
2.03 MB
Format:
Adobe Portable Document Format
License bundle
Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description:
Collections