Developing a reliability model for an 88 kV XLPE cable termination

dc.contributor.authorChimunda, Samantha
dc.date.accessioned2020-09-02T07:31:31Z
dc.date.available2020-09-02T07:31:31Z
dc.date.issued2019
dc.descriptionA research report submitted in partial fulfilment of the requirements for the degree Master of Science in Engineering to the Faculty of Engineering and the Built Environment, School of Electrical and Information Engineering, University of the Witwatersrand, Johannesburg, 2019en_ZA
dc.description.abstractWhereas there are life models for cable systems, the focus has been on cables and not on accessories. Literature shows that cable accessories are the problematic area in cable systems. There is therefore a need to develop cable accessory reliability models which can be used for informed asset management decision. This research work has conceived a reliability model for cable terminations using a case study municipal substation which has been experiencing failure of 88 kV XLPE power cable terminations. In the literature, there is an electrothermal model developed for cable systems. In the present work the existing model was adopted and extended. This study involved identifying the modes of degradation by forensic investigation of the failed terminations. For each mode of degradation, a corresponding mathematical model of the stress life factor was developed. Using the Weakest Link Principle, the product of reliabilities due to each degradation mechanism computes the overall reliability of the termination system. The results indicate that electrothermal stress hardly reduces the reliability of the termination from the time of installation to 40 years in service. However, thermomechanical stress causes a reliability of less than 10% after 18 years and galvanic degradation reduces the termination reliability to less than 10% after 24 years in service. Each new cable termination design should have a corresponding reliability model. The latter entails conducting laboratory aging tests which give the parameters required in developing the stress life factors. For existing terminations, root-cause analysis of failure can lead to determination of the stress factor parameters. The model developed in the present research work can be used in real-time asset management decisions by processing the real time operating conditions.en_ZA
dc.description.librarianTL (2020)en_ZA
dc.facultyFaculty of Engineering and the Built Environmenten_ZA
dc.format.extentOnline resource (vi, 117 leaves)
dc.identifier.citationChimunda, Samantha. (2019). Developing a reliability model for an 88 kV XLPE cable termination. University of the Witwatersrand, https://hdl.handle.net/10539/29424
dc.identifier.urihttps://hdl.handle.net/10539/29424
dc.language.isoenen_ZA
dc.schoolSchool of Electrical and Information Engineeringen_ZA
dc.subject.lcshElectric cables
dc.subject.lcshElectric insulators and insulation
dc.titleDeveloping a reliability model for an 88 kV XLPE cable terminationen_ZA

Files

Original bundle

Now showing 1 - 2 of 2
No Thumbnail Available
Name:
0615922tAbstract.pdf
Size:
244.61 KB
Format:
Adobe Portable Document Format
Description:
Abstract
No Thumbnail Available
Name:
0615922t.pdf
Size:
3.68 MB
Format:
Adobe Portable Document Format
Description:
Main Work

License bundle

Now showing 1 - 1 of 1
No Thumbnail Available
Name:
license.txt
Size:
1.71 KB
Format:
Item-specific license agreed upon to submission
Description:

Collections