Please note: Digitised content is made available at the best possible quality range, taking into consideration file size and the condition of the original item. These restrictions may sometimes affect the quality of the final published item. For queries regarding content of ETD collection please contact IR specialists by email : IR specialists or Tel : 011 717 4652 / 1954

Follow the link below for important information about Electronic Theses and Dissertations (ETD)

Library Guide about ETD

Browse

Search Results

Now showing 1 - 1 of 1
  • Item
    Relationship between corona power loss and audible noise
    (1997) Engelbrecht, Michael Sean
    Results are reported on an initial investigation into corona power loss and its relationship to corona initiated audible noise. The work has the goal of being able to accurately predict the corona power loss, from a transmission line, from knowledge of the audible noise on the line. Corona power loss and its relationship to corona current, applied voltage and electric field is also exarr-ined. Experiments were performed using two single phase, different diameter, corona cages. Although the corona cage test results showed no correlation between corona initiated broad band audible noise and corona power loss, a linear empirical relationship, with excellent correlation, was found to exist between corona power loss and 100Hz Hum (dBA above 20jlPa). Results showed that, at the same magnitude of electric field, within the l h o different diameter corona cages, the corona current is the same magnitude and the corona power loss is proportional to the applied voltage.